Application
Slim DIN mounted RCBO is available as single module devices to save valuable switchboard space.
Specification
Number of Poles | 1P+N |
Line Rated Current(A) | 6, 10, 16, 20, 25, 32 |
Rated Operational Voltage | 230V/240V~ |
Earth-leakage Sensitvity | 10mA, 30mA, 100mA |
Trip Unit Technology | Electronic |
Network Type | AC/A |
Standards | IEC/EN 61009-1 |
Network Frequency | 50/60Hz |
Breaking Capacity | Inc=I△c=6000A |
[Ui] Rated Insulation Voltage | 415V AC |
[Uimp] Rated Impulse Withstand Voltage |
4000V |
Mechanical Durability | 20000 cycles |
Electrical Durability | 10000 cycles |
Tightening Torque | M4 2N.m Ⅱ |
IP Degree of Protection | IP20 comforming to IEC 60529 IP40(modular enclosure) comforming to IEC 60529 |
Curve Code | B,C |
Ambient Air Temperature for Operation |
-5~40°C |
EU RoHS Directive | Compliant EU RoHS Declaration |
Pollution Degree | 2 comforming to IEC/EN 60898-1 |
Upper Wiring Lower Wiring |
![]() ![]() |
Dimensions