Bar Fuse Switch Disconnector

Basic Information
  1. Model BFD1,BFD2,BFD3

Product Description

Application

BFD1 BFD2 BFD3 series fuse switch disconnector is integrated with initiating current transformer and fuse switch in circuit with rated working current of 160A, 250A, 400A, 630A or 800A 50/60Hz. These fuse switch disconnectors provide reliable overload and short circuit protection for distribution facility, such as cable branch box, box transformer in industrial plants, cormnunity and other infrastructure as well.

  • The location of the switch installation is no more than 2000m.
  • The level of environmental pollution of the switch is grade 3.
  • The installation category of the switch is class lll.
  • The switch is installed in a place where there is no vibration or shock
  • Fuse units of BFD3 model are closed or opened integrately while fuse unites under BFD2 model are operated separately only.
  • The operation is safer, the core is mounted on the handle, and can be used directly as contact blades;
  • Beautiful and practical, seat and body disassembly convenience, and box installation fast, convenient construction.
  • Reduce wiring, easy to increase the loop. Increase the use rate of the box;
  • Resin glass fiber base, V0 grade flame retardant, and the protection grade of shell can reach P30;
  • New products, H field, he used semi tender 7l bid to develop styles.
  • Instantaneous time off up to 100KA, with a load capacity of up to 1.3 times of rated current;
  • Can add fuse monitor, signal switch and remote control module.

Specification

Model BFD1-1 60 BFD1-250 BFD1-400 BFD1-630
Rated Operational Voltage (Ue) 690V
Rated Operational Current (le) 160A 250A 400A 630A
Fuse Size 00 1 2 3
Rated Insulation Voltage (Ui) 1000V
Rated Impulse Withstand Voltage (Uimp) 12KV
Degree of Protection IP10
Mechanica Life (times) 2000
Wire Specifications 10-95mm2 120mm2 240mm2 300mm2
Method Connecting Wire Screw & V-Clamp
Installation Method Screw & Hook
Use Classes AC-21B AC-22B AC-23B
Standard IEC/EN60947-3
Rated Short Circuit Current (q) 120KA
Rated Short Time Current (Icw) 16KA/1s
Screw Fastening M8/M10/M12
Ambinet Temperature -45°C~+50°C
Model BFD2-160 BFD2-250 BFD2-400 BFD2-630 BFD2-800
Rated Operational Voltage (Ue) 690V
Rated Operational Current (le) 1 60A 250A 400A 630A 800A
Fuse Size 00 1 2 3 3
Rated Insulation Voltage (Ui) 1000V
Rated Impulse Withstand Voltage (Uimp) 12KV
Degree of Protection IP20
Mechanica Life (times) 2000
Wire Specifications 10-70mm2 120mm? 240mm2 300mm2 2x240mm2
Method Connecting Wire Screw & V-Clamp
Installation Method Screw & Hook
Use Classes AC-21B AC-22B AC-23B
Standard IEC/EN60947-3
Rated Short Circuit Current (q) 120KA
Rated Short Time Current (Icw) 16KA/1s
Screw Fastening M8/M 10/M12
Ambinet Temperature -45°C~+50°C
Model BFD3-160 BFD3-250 BFD3-400 BFD3-630 BFD3-800
Rated Operational Voltage (Ue) 690V
Rated Operational Current (le) 160A 250A 400A 630A 800A
Fuse Size 00 1 2 3 3
Rated Insulation Voltage (Ui) 1000V
Rated Impulse Withstand Voltage (Uimp) 12KV
Degree of Protection IP20
Mechanica Life (times) 2000
Wire Specifications 10-70mm2 120mm2 240mm2 300mm2 2x240mm2
Method Connecting Wire Screw & V-Clamp
Installation Method Screw & Hook
Use Classes AC-21B AC-22B AC-23B
Standard IEC/EN60947-3
Rated Short Circuit Current (q) 120KA
Rated Short Time Current (Icw) 16KA/1s
Screw Fastening M8/M 10/M12
Ambinet Temperature -45°C~+55°C

Dimensions

We have more than 31 years experience

Our Strength

1994
Founded
31+
Patent
49+
Agents
1000+
Clients

Request a Quote